Title : - Diagnosis of the Senegalese electricity transmission network- SENELEC
Author : Finck, Hugo ULiège
Date of defense  : 7-Sep-2026/8-Sep-2026
Advisor(s) : Cornélusse, Bertrand ULiège
Committee's member(s) : Dewallef, Pierre ULiège
Louveaux, Quentin ULiège
Language : English
Discipline(s) : Engineering, computing & technology > Energy
Institution(s) : Université de Liège, Liège, Belgique
Degree: Master : ingénieur civil en génie de l'énergie à finalité spécialisée en Energy Networks
Faculty: Master thesis of the Faculté des Sciences appliquées

Abstract

[en] The Senegalese electricity transmission network is undergoing a massive structural and
technological transition, driven by an average annual demand growth of 11.9%, the rapid
integration of intermittent renewable energies (targeting 40% by 2030), and the national
Gas-to-Power strategy. These dynamics generate highly volatile and bidirectional power
flows, shifting the system’s vulnerabilities towards static security and rendering traditional
snapshot-based grid planning obsolete. This thesis addresses this challenge by providing a
comprehensive prospective diagnosis of the interconnected grid for the 2025 reference year
(culminating in a peak demand of 1,261 MW), achieved through the development of a fully
automated digital twin in the open-source Python/Pandapower environment.
To ensure industrial-grade accuracy and replicate physical grid operations, automated dynamic
controllers (such as On-Load Tap Changers and shunt reactors) were explicitly modeled. The
digital twin was rigorously calibrated against PSS/E using single-objective and multi-objective
metaheuristic algorithms (Differential Evolution and Optuna). Crucially, this optimization
framework acted as a physical anomaly detector, identifying and rectifying an underlying
structural discrepancy in the transformer MVA base conversion. Once analytically corrected,
the Pandapower model achieved near-perfect alignment with PSS/E reference data, reducing
the nodal voltage Mean Absolute Error (MAE) to a negligible 0.0005 p.u.
Leveraging this validated model, chronological steady-state (N-0) and contingency (N-1)
simulations were executed over the 8,760 hours of the reference year. The systemic analysis
revealed a deeply polarized grid. During off-peak periods, the lightly loaded 225 kV infras-
tructure behaves as a massive capacitor, generating a net reactive power surplus (Ferranti
effect) that forces urban 90 kV substations into chronic overvoltage states (reaching up to
1.15 p.u.). Conversely, evening load peaks and N-1 contingencies trigger critical bottlenecks
on the Dakar peninsula, with evacuation corridors facing severe cascading overloads up to
154% of their ampacity. Furthermore, the analysis highlighted severe localized vulnerabilities,
such as radial antenna weaknesses in the southern Casamance grid, where a single line trip
systematically leads to localized blackouts.
To secure the network, a multi-horizon operational and infrastructural roadmap was formulated.
In the short term, zero-CAPEX preventive line switching and optimized static retuning of
primary transformer off-load taps are proposed to provide immediate relief. For the medium
term, the algorithmic sizing and deployment of 75 MVAr of Variable Shunt Reactors (VSR)
at strategic nodes (Patte d’Oie and Tobene) is validated to definitively neutralize capacitive
overvoltages. Finally, as a long-term structural solution, High-Temperature Low-Sag (HTLS)
reconductoring is recommended for the congested 90 kV industrial corridors. This innovative
approach doubles thermal ampacity while retaining the existing pylons, thereby avoiding the
significant delays associated with building a new line.


File(s)

Document(s)

File
Access Abstract_Hugo_Finck.pdf
Description:
Size: 88.72 kB
Format: Adobe PDF
File
Access TFE_Hugo_Finck.pdf
Description:
Size: 13.33 MB
Format: Adobe PDF

Author

  • Finck, Hugo ULiège Université de Liège > Mast. ing. civ. gén. énerg. fin. spéc. Net.

Promotor(s)

Committee's member(s)

  • Dewallef, Pierre ULiège Université de Liège - ULiège > Département d'aérospatiale et mécanique > Systèmes de conversion d'énergie pour un dévelop.durable
    ORBi View his publications on ORBi
  • Louveaux, Quentin ULiège Université de Liège - ULiège > Dép. d'électric., électron. et informat. (Inst.Montefiore) > Systèmes et modélisation : Optimisation discrète
    ORBi View his publications on ORBi








All documents available on MatheO are protected by copyright and subject to the usual rules for fair use.
The University of Liège does not guarantee the scientific quality of these students' works or the accuracy of all the information they contain.