Feedback

Faculté des Sciences appliquées
Faculté des Sciences appliquées
MASTER THESIS

Modeling and trade-off analysis of a condenser with thermoelectric generation

Download
Boden, Matthieu ULiège
Promotor(s) : Gendebien, Samuel ULiège
Date of defense : 7-Sep-2026/8-Sep-2026 • Permalink : http://hdl.handle.net/2268.2/27601
Details
Title : Modeling and trade-off analysis of a condenser with thermoelectric generation
Author : Boden, Matthieu ULiège
Date of defense  : 7-Sep-2026/8-Sep-2026
Advisor(s) : Gendebien, Samuel ULiège
Committee's member(s) : Lemort, Vincent ULiège
Dewallef, Pierre ULiège
Hernandez Naranjo, Jairo Andres ULiège
Language : English
Discipline(s) : Engineering, computing & technology > Energy
Institution(s) : Université de Liège, Liège, Belgique
Degree: Master : ingénieur civil en génie de l'énergie à finalité spécialisée en Energy Conversion
Faculty: Master thesis of the Faculté des Sciences appliquées

Abstract

[en] A transverse thermoelectric generator turns a heat exchanger tube into an electrical source
without discrete junctions, ceramic substrates or interface layers, because the tube wall itself
is the active medium. Existing work on such devices treats their thermal problem locally,
with constant heat-transfer coefficients and a fixed tube length. That treatment is adequate
for the single-phase device in which the architecture was demonstrated, and it is not adequate
for a condenser, where the local heat flux collapses by close to an order of magnitude at the
completion of condensation. This thesis develops a one-dimensional, segment-resolved model
of a two-phase condenser whose wall is a transverse thermoelectric laminate, with bidirectional
coupling between the thermal and the electrical problems.
The tube is divided into segments in which the refrigerant state, the wall temperatures and
the local thermoelectric quantities are solved together. The tilted metal and semiconductor
laminate is reduced to effective transport properties by rotation of the transport tensors,
condensation is closed by a three-regime correlation, and the segments are coupled by a single
current. That current makes the electrical problem global while the thermal driving remains
local, which is the structural feature the analysis exploits. Because the Seebeck and Peltier
coefficients are one material property, the current returns into the wall boundary condition
rather than following from it.
Verification rests on conservation balances, grid convergence and limiting cases whose
answer is known in advance. The two halves of the model are validated against independent
measurements: the thermoelectric half against a manufactured tubular device, through a single
fitted parameter representing the interfacial electrical contact resistance, and the condensation
closure against measured quasi-local coefficients, which it reproduces to about 1 % in the
shear-dominated regime without any adjusted parameter.
Applied to a reference condenser, the model shows that the thermoelectric wall first imposes
a thermal penalty, the effective conductivity falling from 20 W/(m K) to 13.9 W/(m K) . Closing
the circuit delivers 42.1 mW against a duty of about 315 W, a system efficiency of 1.3 × 10−4.
Roughly half the segments deliver negative power, occupying the subcooled region where the
driving temperature difference is too small to sustain the common current, and 28.7 % of the
gross production is destroyed internally before reaching the terminals. The sensitivity analysis
ranks the parameters that remain once the laminate is taken as manufactured: power falls
with tube length beyond the condensation zone, wall thickness is the strongest exchanger lever,
the shell diameter is inert, and the conditions under which the device is installed outweigh
the geometry around it. The conversion efficiency is negligible and the device is not an energy-recovery technology
at this operating point. Its interest lies in the local coupling, which only a segment-resolved
approach reveals: half the tube works against the other half, and that loss carries its own
remedy in the form of an electrical partition at the phase boundary. The absolute levels rest
on a fitted electrical parameter, omit an interfacial thermal resistance and use a condensation
closure extrapolated below its validated domain, so they are reported as a preliminary mapping
of an immature architecture rather than as a performance figure.

Author

  • Boden, Matthieu ULiège Université de Liège > Mast. ing. civ. gén. énerg. fin. spéc. Energ. conv.

Promotor(s)

Committee's member(s)

  • Lemort, Vincent ULiège Université de Liège - ULiège > Département d'aérospatiale et mécanique > Systèmes énergétiques
    ORBi View his publications on ORBi
  • Dewallef, Pierre ULiège Université de Liège - ULiège > Département d'aérospatiale et mécanique > Systèmes de conversion d'énergie pour un dévelop.durable
    ORBi View his publications on ORBi
  • Hernandez Naranjo, Jairo Andres ULiège Université de Liège - ULiège > Département d'aérospatiale et mécanique > Systèmes énergétiques
    ORBi View his publications on ORBi








All documents available on MatheO are protected by copyright and subject to the usual rules for fair use.
The University of Liège does not guarantee the scientific quality of these students' works or the accuracy of all the information they contain.